Temporary Heaters on a Construction Site: OSHA's Rules for Ventilation, Clearances and Salamanders (29 CFR 1926.154)

OSHA's construction rule 29 CFR 1926.154 covers temporary heating devices: fresh air in sufficient quantity (mechanical ventilation where natural air is not enough), minimum clearances to combustible material from Table F-4, an insulating base under heaters not suitable for wood floors, at least 10 feet from combustible tarpaulins, level setting, no solid fuel salamanders in buildings or on scaffolds, and a flame-failure safety control on oil-fired heaters.

OSHA construction safetyExplainerPublished

Fact-checked against official sources · Last checked

Card reading OSHA construction safety, Explainer: Temporary heaters on site, ventilation, clearances, salamanders, 29 CFR 1926.154. eCFR, Nov 25, 2026
Image: goraedu · Own work

OSHA's construction rules give temporary heaters their own section: 29 CFR 1926.154, "Temporary heating devices," in Subpart F (Fire Protection and Prevention). This explainer answers one practical question: what does OSHA require when a temporary heater is used on a jobsite? It reads the section as it stands in the eCFR (text current to November 23, 2026). It is an explainer, not a rule change. It covers construction work under Part 1926.

Is there enough fresh air?

1926.154(a)(1) states: "Fresh air shall be supplied in sufficient quantities to maintain the health and safety of workmen. Where natural means of fresh air supply is inadequate, mechanical ventilation shall be provided."

For confined spaces, 1926.154(a)(2) adds: "When heaters are used in confined spaces, special care shall be taken to provide sufficient ventilation in order to ensure proper combustion, maintain the health and safety of workmen, and limit temperature rise in the area."

The section does not set a number of air changes or a gas level; it states the purposes the ventilation must serve.

How far from combustible material?

Under 1926.154(b)(1), "Temporary heating devices shall be installed to provide clearance to combustible material not less than the amount shown in Table F-4." The table gives these minimum clearances in inches:

Heating applianceSidesRearChimney connector
Room heater, circulating type121218
Room heater, radiant type363618

A heater can be closer only if its listing allows it. 1926.154(b)(2) states: "Temporary heating devices, which are listed for installation with lesser clearances than specified in Table F-4, may be installed in accordance with their approval."

Can a heater sit on a wood floor?

Only if it is suitable for that. 1926.154(b)(3) says "Heaters not suitable for use on wood floors shall not be set directly upon them or other combustible materials. When such heaters are used, they shall rest on suitable heat insulating material or at least 1-inch concrete, or equivalent. The insulating material shall extend beyond the heater 2 feet or more in all directions."

What about tarps and enclosures?

For coverings such as tarps, 1926.154(b)(4) states: "Heaters used in the vicinity of combustible tarpaulins, canvas, or similar coverings shall be located at least 10 feet from the coverings. The coverings shall be securely fastened to prevent ignition or upsetting of the heater due to wind action on the covering or other material."

Does the heater have to be level?

Yes, unless the maker says otherwise. Under 1926.154(c), "Heaters, when in use, shall be set horizontally level, unless otherwise permitted by the manufacturer's markings."

Are salamanders allowed?

Not the solid fuel kind indoors or on scaffolds. 1926.154(d) is one sentence: "Solid fuel salamanders are prohibited in buildings and on scaffolds."

Rules for oil-fired heaters

1926.154(e) covers heaters that burn liquid fuel:

  • "Flammable liquid-fired heaters shall be equipped with a primary safety control to stop the flow of fuel in the event of flame failure. Barometric or gravity oil feed shall not be considered a primary safety control." (1926.154(e)(1))
  • "Heaters designed for barometric or gravity oil feed shall be used only with the integral tanks." (1926.154(e)(2))
  • "Heaters specifically designed and approved for use with separate supply tanks may be directly connected for gravity feed, or an automatic pump, from a supply tank." (1926.154(e)(4))

Paragraph (e)(3) is reserved. Heaters that use liquefied petroleum gas also have rules in 29 CFR 1926.153, "Liquefied petroleum gas (LP-Gas)," which this post does not cover.

What this means for study

Section 1926.154 is not in our construction study guides. Our OSHA construction general safety study guide and practice test cover other construction rules, and more is on our OSHA construction page.