Shops that weld or cut with oxygen and a fuel gas often feed their stations from fixed pipe instead of single cylinders. OSHA's general industry rule for this work, 29 CFR 1910.253, "Oxygen-fuel gas welding and cutting," covers that pipe in paragraph (d), "Service piping systems." This explainer answers one practical question: what does 1910.253(d) require for the material, joints, installation and testing of that piping? It reads the section in the eCFR (text up to date as of November 25, 2026). It is an explainer, not a rule change, and it does not cover the construction rules in 29 CFR 1926 Subpart J.
What can the pipe be made of?
Under 1910.253(d)(1)(i)(B), "Piping shall be steel, wrought iron, brass or copper pipe, or seamless copper, brass or stainless steel tubing," except as the next two paragraphs provide. Piping and fittings must also comply with section 2 of ANSI B31.1 (1967), which the rule incorporates by reference, except where it conflicts with two rules in (d)(1)(i)(A):
- "Pipe shall be at least Schedule 40 and fittings shall be at least standard weight in sizes up to and including 6-inch nominal."
- "Copper tubing shall be Types K or L" under ASTM B88-66a.
The gas-specific limits are short:
- High-pressure oxygen: "Oxygen piping and fittings at pressures in excess of 700 psi (4.8 MPa), shall be stainless steel or copper alloys" (d)(1)(ii)(A).
- Acetylene: "Piping for acetylene or acetylenic compounds shall be steel or wrought iron" (d)(1)(iii)(A), and "Unalloyed copper shall not be used for acetylene or acetylenic compounds except in listed equipment" (d)(1)(iii)(B).
Can hose be used between a manifold and the pipe?
Only within limits. Paragraph (d)(1)(ii)(B) allows hose and hose connections meeting 1910.253(e)(5) to connect the outlet of a manifold pressure regulator to piping "providing the working pressure of the piping is 250 psi (1.7 MPa) or less and the length of the hose does not exceed 5 feet (1.5 m)." The hose must have a minimum bursting pressure of 1,000 psig. When oxygen comes from a low-pressure oxygen manifold with no pressure regulating device in between, the piping system must have a minimum design pressure of 250 psig, and a regulating device is required at each station outlet when the connected equipment is for use below 250 psig (d)(1)(ii)(C).
How must joints be made?
- Steel or wrought iron pipe: joints "shall be welded, threaded or flanged." Fittings may be rolled, forged or cast steel, malleable iron or nodular iron, and "Gray or white cast iron fittings are prohibited" (d)(2)(i).
- Brass or copper pipe: joints shall be welded, brazed, threaded or flanged; socket-type joints are brazed with silver-brazing alloy or a similar filler metal melting at not less than 800 °F (427 °C) (d)(2)(ii).
- Seamless copper, brass or stainless steel tubing: approved gas tubing fittings or brazed joints, with the same 800 °F rule for socket-type joints (d)(2)(iii).
What does the rule say about installing the pipe?
Paragraph (d)(3) includes these points, among others:
- Piping is run as directly as practicable and protected against physical damage; pipe laid underground in earth is placed below the frost line and protected against corrosion (d)(3)(ii).
- "Only piping which has been welded or brazed shall be installed in tunnels, trenches or ducts," with shutoff valves outside those conduits. Oxygen piping may share a tunnel, trench or duct with fuel-gas lines "provided there is good natural or forced ventilation" (d)(3)(iii).
- Every building gets readily accessible gas cocks or valves for shutting off the supply in an emergency, plus a shutoff valve in the discharge line from the source of supply (d)(3)(v).
- Oxygen piping and fittings are washed out with a solution that removes grease and dirt "but will not react with oxygen" (d)(3)(vii).
- After assembly, oxygen piping is blown out only with "oil-free air, oil-free nitrogen, or oil-free carbon dioxide" (d)(3)(ii) and (d)(3)(viii).
- "No welding or cutting shall be performed on an acetylene or oxygen pipeline, including the attachment of hangers or supports, until the line has been purged" (d)(3)(x).
How is the system marked and tested?
Aboveground piping is marked under ANSI A13.1-1956, and "Station outlets shall be marked to indicate the name of the gas" (d)(4)(ii) and (iii). Under (d)(5)(i), "Piping systems shall be tested and proved gastight at 1 1/2 times the maximum operating pressure, and shall be thoroughly purged of air before being placed in service." The material used to test oxygen lines must be oil free and noncombustible, and "Flames shall not be used to detect leaks."
Where to study the rest of Subpart Q
Our OSHA general industry welding study guide covers fire precautions, ventilation, cylinders and arc welding under Subpart Q; it notes that service piping is not covered there in detail. For how welding certification works, see our welding page. OSHA rules are safety requirements, not a welding certification exam; this post does not describe any certification test.