goraedu

What Happens When a Water System Exceeds a TTHM or HAA5 Operational Evaluation Level? 40 CFR 141.626

Under the Stage 2 disinfection byproducts rule (40 CFR 141 Subpart V), a system exceeds the operational evaluation level at a monitoring location when the two previous quarters' results plus twice the current quarter's result, divided by 4, is above 0.080 mg/L for TTHM or 0.060 mg/L for HAA5. It must then conduct an operational evaluation and send a written report to the State no later than 90 days after being notified of the result (40 CFR 141.626).

Drinking water operatorExplainerPublished

Fact-checked against official sources · Last checked

Card reading Drinking water operator, Explainer: TTHM and HAA5 operational evaluation levels, 40 CFR 141.626. Source: eCFR. Nov 28, 2026
Image: goraedu · Own work

Total trihalomethanes (TTHM) and haloacetic acids (five) (HAA5) are disinfection byproducts with maximum contaminant levels in 40 CFR 141.64. Under the Stage 2 rule in 40 CFR 141 Subpart V, compliance is judged location by location, and the rule also sets an operational evaluation level (141.626). This explainer answers one practical question from the eCFR text: when is that level exceeded, and what must the water system do next? It is an explainer, not a rule change.

Which systems does Subpart V cover?

Section 141.620(b) states: "You are subject to these requirements if your system is a community water system or a nontransient noncommunity water system that uses a primary or residual disinfectant other than ultraviolet light or delivers water that has been treated with a primary or residual disinfectant other than ultraviolet light."

The MCLs that apply under Subpart V are in 141.64(b)(2)(i): 0.080 mg/L for TTHM and 0.060 mg/L for HAA5, which "must be complied with as a locational running annual average at each monitoring location" beginning on the Subpart V compliance date in 141.620(c).

When is the operational evaluation level exceeded?

Section 141.626(a) gives the calculation. A system has exceeded the operational evaluation level "at any monitoring location where the sum of the two previous quarters' TTHM results plus twice the current quarter's TTHM result, divided by 4 to determine an average, exceeds 0.080 mg/L, or where the sum of the two previous quarters' HAA5 results plus twice the current quarter's HAA5 result, divided by 4 to determine an average, exceeds 0.060 mg/L."

In other words, it uses three quarters of results at one location, with the current quarter counted twice:

  • TTHM: (previous quarter 2 + previous quarter 1 + 2 × current quarter) ÷ 4, compared with 0.080 mg/L.
  • HAA5: the same calculation, compared with 0.060 mg/L.

This is a different number from the locational running annual average (LRAA) used for MCL compliance. Under 141.625(b), a system is in violation of the MCL "when the LRAA exceeds the subpart V MCLs in § 141.64(b)(2), calculated based on four consecutive quarters of monitoring" (or fewer quarters if the MCL would be exceeded regardless of later results).

What must the system do after an exceedance?

Section 141.626(b)(1) states: "If you exceed the operational evaluation level, you must conduct an operational evaluation and submit a written report of the evaluation to the State no later than 90 days after being notified of the analytical result that causes you to exceed the operational evaluation level." It adds: "The written report must be made available to the public upon request."

The 90 days run from when the system is notified of the analytical result (141.626(b)(1)).

What does the operational evaluation look at?

Under 141.626(b)(2), the evaluation "must include an examination of system treatment and distribution operational practices, including storage tank operations, excess storage capacity, distribution system flushing, changes in sources or source water quality, and treatment changes or problems that may contribute to TTHM and HAA5 formation and what steps could be considered to minimize future exceedances."

Can the evaluation be narrower?

Yes, with State approval. Section 141.626(b)(2)(i) states: "You may request and the State may allow you to limit the scope of your evaluation if you are able to identify the cause of the operational evaluation level exceedance."

Two conditions follow in (b)(2)(ii): the request "does not extend the schedule in paragraph (b)(1) of this section for submitting the written report," and "The State must approve this limited scope of evaluation in writing and you must keep that approval with the completed report."

How is the exceedance reported?

Separately from the evaluation report, the quarterly report under 141.629(a)(1) must be sent to the State "within 10 days of the end of any quarter in which monitoring is required." For each monitoring location it includes, under 141.629(a)(1)(v): "Any operational evaluation levels that were exceeded during the quarter and, if so, the location and date, and the calculated TTHM and HAA5 levels." Under 141.629(b), Subpart V monitoring plans and results are kept "as required by § 141.33."

Does a single high sample change the monitoring schedule?

It can. Section 141.625(a) says a system that monitors a location "annually or less frequently than annually under § 141.621 or § 141.623" must "increase monitoring to dual sample sets once per quarter (taken every 90 days) at all locations if a TTHM sample is >0.080 mg/L or a HAA5 sample is >0.060 mg/L at any location." Under 141.625(c), it may return to routine monitoring after at least four consecutive quarters of increased monitoring when "the LRAA for every monitoring location is ≤0.060 mg/L for TTHM and ≤0.045 mg/L for HAA5."

Where to check before you act

These are the requirements as shown in the eCFR on the date checked. EPA and the State primacy agency are the authorities, and footnote 1 to the table in 141.620(c) notes that "The State may grant up to an additional 24 months for compliance with MCLs and operational evaluation levels if you require capital improvements to comply with an MCL." Our disinfectant residuals and byproducts study guide covers the Subpart L rules (Subpart V is not part of that guide), and the drinking water operator page lists our other study guides and practice tests.

goraedu is independent and is not affiliated with or endorsed by the U.S. EPA or any government agency.

Sources

Found an error? Email [email protected]. We review reports within 7 days and log fixes on the corrections page.