EPA 608 Type I practice test

47 free practice questions on the Type I section. Each answer is explained and linked to the official source it comes from.

Fact-checked against official sources · Last checked

EPA 608 Type I

47 questions across 6 topics. After each answer you see why it is right, with a link to the official source.

Tip: press A, B, C or D to answer and Enter for the next question. Nothing you answer leaves your browser.

Review all 47 questions

Prefer to read? Here is every question in the EPA 608 Type I set, grouped by topic. Open a question to see the answer, why it is right and the official source.

Definitions

  1. 1. A university lab buys a research freezer that holds 3 pounds of refrigerant. How does the small appliance definition treat medical or industrial research refrigeration equipment?

    • A. It names it as an example of a small appliance
    • B. It excludes all research equipment from the small appliance category
    • C. It treats it as industrial process refrigeration
    • D. It treats it as an MVAC-like appliance
    Show answer

    Answer: A. It names it as an example of a small appliance

    The small appliance definition lists examples that include "medical or industrial research refrigeration equipment," provided the appliance is factory-sealed with five pounds or less of refrigerant.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  2. 2. The definition of "appliance" covers devices that contain and use a class I or class II substance or substitute as a refrigerant. For which purposes must the device be used?

    • A. Only industrial process purposes
    • B. Only military purposes
    • C. Household or commercial purposes
    • D. Only motor vehicle purposes
    Show answer

    Answer: C. Household or commercial purposes

    Appliance means any such device "which is used for household or commercial purposes, including any air conditioner, motor vehicle air conditioner, refrigerator, chiller, or freezer." The definition is not limited to industrial, military or vehicle use.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  3. 3. According to its definition, when can a process stub be resealed?

    • A. At the conclusion of repair or service
    • B. Only before any refrigerant has been recovered
    • C. Only when the appliance is disposed of
    • D. Never; it is cut open and left that way
    Show answer

    Answer: A. At the conclusion of repair or service

    A process stub is a length of tubing giving access to the refrigerant in a small appliance or room air conditioner "that can be resealed at the conclusion of repair or service." It is designed to be closed again after the work, not left open or used only at disposal.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  4. 4. Under the definitions, what is a self-sealing valve?

    • A. A valve affixed to a container of refrigerant that automatically seals when not dispensing refrigerant
    • B. A length of tubing that is resealed after service
    • C. The part of an appliance that holds the charge during service
    • D. An opening built into an appliance for removing refrigerant at disposal
    Show answer

    Answer: A. A valve affixed to a container of refrigerant that automatically seals when not dispensing refrigerant

    A self-sealing valve is "a valve affixed to a container of refrigerant that automatically seals when not dispensing refrigerant" and meets the criteria in 82.154(c)(2). The other options describe a process stub, a system receiver and a servicing aperture.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  5. 5. Under the definitions, what is a one-time expansion device?

    • A. A valve on a refrigerant container that seals automatically
    • B. An appliance that relies on the release of its refrigerant charge to the environment to provide a cooling effect
    • C. A vessel within an appliance that holds the charge during service
    • D. A length of tubing that gives access to the refrigerant in a small appliance
    Show answer

    Answer: B. An appliance that relies on the release of its refrigerant charge to the environment to provide a cooling effect

    A one-time expansion device is "an appliance that relies on the release of its refrigerant charge to the environment in order to provide a cooling effect." Under 82.154(f), one may be made or imported only if all its refrigerants are exempt.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  6. 6. Recycled refrigerant is generally cleaned using oil separation and single or multiple passes through which kind of device?

    • A. Distillation columns at a reclamation plant
    • B. Replaceable core filter-driers
    • C. Process stubs
    • D. Self-sealing valves
    Show answer

    Answer: B. Replaceable core filter-driers

    The definition of recycle says recycled refrigerant is cleaned "using oil separation and single or multiple passes through devices, such as replaceable core filter-driers, which reduce moisture, acidity, and particulate matter." Process stubs and self-sealing valves are access and container fittings, not cleaning devices.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  7. 7. The definition of small appliance lists room air conditioners as an example. Which kind of equipment does it name as included among room air conditioners?

    • A. MVAC-like appliances
    • B. Motor vehicle air conditioners
    • C. Industrial process refrigeration
    • D. Packaged terminal air heat pumps
    Show answer

    Answer: D. Packaged terminal air heat pumps

    The definition lists "room air conditioners (including window air conditioners, portable air conditioners, and packaged terminal air heat pumps)." MVACs and MVAC-like appliances are separate categories with their own rules, and industrial process refrigeration is not named in the small appliance definition.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  8. 8. The definition of small appliance names refrigerators and freezers designed for which uses?

    • A. Home, commercial, or consumer use
    • B. Home use only
    • C. Commercial use only
    • D. Military use only
    Show answer

    Answer: A. Home, commercial, or consumer use

    The definition includes "refrigerators and freezers (designed for home, commercial, or consumer use)." It is not limited to home or commercial units alone.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  9. 9. A technician paints a household refrigerator. How does the technician definition classify painting the appliance?

    • A. As opening the appliance
    • B. As an activity not reasonably expected to violate the integrity of the refrigerant circuit
    • C. As disposal of the appliance
    • D. As work that only a Type I technician may perform
    Show answer

    Answer: B. As an activity not reasonably expected to violate the integrity of the refrigerant circuit

    The rule says activities "such as painting the appliance, rewiring an external electrical circuit, replacing insulation on a length of pipe, or tightening nuts and bolts are not reasonably expected to violate the integrity of the refrigerant circuit." Painting does not release refrigerant, so it is not opening or disposal.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  10. 10. According to the technician definition, activities on an appliance that has been properly evacuated under 40 CFR 82.156 are not reasonably expected to release refrigerants unless the activity includes what?

    • A. Painting the appliance
    • B. Tightening nuts and bolts
    • C. Rewiring an external electrical circuit
    • D. Adding refrigerant to the appliance
    Show answer

    Answer: D. Adding refrigerant to the appliance

    Activities on properly evacuated appliances "are not reasonably expected to release refrigerants unless the activity includes adding refrigerant to the appliance." Painting, tightening nuts and bolts and rewiring an external circuit are listed as activities not expected to violate the refrigerant circuit.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  11. 11. During service, a person attaches hoses and gauges to a drinking water cooler that is a small appliance. How does the technician definition classify attaching hoses and gauges to an appliance?

    • A. As an activity, like painting the appliance, that is not reasonably expected to violate the integrity of the refrigerant circuit
    • B. As disposal of the appliance
    • C. As opening the appliance
    • D. As an activity reasonably expected to violate the integrity of the refrigerant circuit
    Show answer

    Answer: D. As an activity reasonably expected to violate the integrity of the refrigerant circuit

    Activities reasonably expected to violate the integrity of the refrigerant circuit include "Attaching or detaching hoses and gauges to and from the appliance; adding or removing refrigerant; adding or removing components; and cutting the refrigerant line." Under the separate definition of opening an appliance, connecting and disconnecting hoses and gauges "are not considered" opening an appliance.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  12. 12. A household refrigerator is charged with a hydrofluoroolefin refrigerant used in place of a class I or class II ozone-depleting substance. How do the definitions classify that refrigerant?

    • A. As a class I substance
    • B. As a class II substance
    • C. As a recovery efficiency standard
    • D. As a substitute
    Show answer

    Answer: D. As a substitute

    Substitute means "any chemical or product, whether existing or new, that is used as a refrigerant to replace a class I or II ozone-depleting substance", and the listed examples include "hydrofluoroolefins". Class I and class II refer to ozone-depleting substances listed in subpart A.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

Equipment

  1. 13. Small appliances normally must be equipped with a process stub before they can be sold. Which small appliances are excepted from that requirement?

    • A. Those holding less than one pound of refrigerant
    • B. Those sold for export
    • C. Those containing only refrigerants exempted under 40 CFR 82.154(a)(1)
    • D. Those sold only to certified technicians
    Show answer

    Answer: C. Those containing only refrigerants exempted under 40 CFR 82.154(a)(1)

    No one may sell or distribute a small appliance "(except appliances containing only refrigerants that have been exempted under paragraph (a)(1) of this section)" unless it has a process stub. The rule sets no exception for charge size, export or the buyer's certification.

    Source: eCFR: 40 CFR 82.154, Prohibitions (as of Nov 3, 2026)

  2. 14. How must recovery and/or recycling equipment be used?

    • A. According to the equipment manufacturer's directions, unless they conflict with the regulation
    • B. Only as described by the technician certification program
    • C. Only as described by the appliance manufacturer
    • D. However the technician prefers, as long as the recovery level is met
    Show answer

    Answer: A. According to the equipment manufacturer's directions, unless they conflict with the regulation

    All recovery and/or recycling equipment "must be used in accordance with the manufacturer's directions" unless those directions conflict with the requirements of the subpart. The rule points to the equipment maker's directions, not the technician's preference or the certifying program.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  3. 15. A shop alters the design of its certified small-appliance recovery machine in a way that affects its ability to meet the certification standards. Until the altered design is tested and shown to meet them, how is the machine treated?

    • A. As certified, because the original model was certified
    • B. As certified for 90 days
    • C. As uncertified
    • D. As certified if a Type I technician approves the change
    Show answer

    Answer: C. As uncertified

    No one may alter certified equipment this way without resubmitting the design for testing, and "Until it is tested and shown to meet the certification standards in this section, equipment so altered will be considered uncertified." The original certification does not carry over to the altered machine.

    Source: eCFR: 40 CFR 82.158, Standards for recovery and/or recycling equipment (as of Nov 3, 2026)

  4. 16. A technician recovers refrigerant from a small appliance that contains a class I or class II refrigerant or a non-exempt substitute. Under 40 CFR 82.154(b)(2), the recovery and/or recycling equipment must be certified under 40 CFR 82.158 for what?

    • A. Any one refrigerant, which then covers all others
    • B. The refrigerant only, whatever the type of appliance
    • C. MVACs only
    • D. That type of refrigerant and appliance
    Show answer

    Answer: D. That type of refrigerant and appliance

    No one may service such an appliance without "using recovery and/or recycling equipment that is certified for that type of refrigerant and appliance under § 82.158." Certification for the refrigerant alone, or for MVACs, does not meet this rule.

    Source: eCFR: 40 CFR 82.154, Prohibitions (as of Nov 3, 2026)

  5. 17. Besides the certification statement, what must the label on certified small-appliance recovery equipment show?

    • A. The technician's certification number
    • B. The owner's name and address
    • C. The date of manufacture and the serial number (if applicable)
    • D. The date the equipment was last used
    Show answer

    Answer: C. The date of manufacture and the serial number (if applicable)

    Labels on equipment certified under 82.158(d) and (e) "must also show the date of manufacture and the serial number (if applicable) of the equipment." The rule does not ask for a technician's number, an owner's details or a date of last use on the label.

    Source: eCFR: 40 CFR 82.158, Standards for recovery and/or recycling equipment (as of Nov 3, 2026)

Recovery requirements

  1. 18. With small-appliance recovery equipment made on or after November 15, 1993, which fact decides whether the 90 percent or the 80 percent recovery level applies?

    • A. The type of refrigerant in the appliance
    • B. Whether the compressor in the appliance is functioning
    • C. The age of the appliance
    • D. The type of certification the technician holds
    Show answer

    Answer: B. Whether the compressor in the appliance is functioning

    With this equipment, technicians recover 90 percent "when the compressor in the appliance is functioning," or 80 percent "when the compressor in the appliance is not functioning." The rule ties the level to the compressor, not to the refrigerant, appliance age or certification type.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  2. 19. A technician uses a certified recovery machine built in 2019 on a dormitory refrigerator whose compressor has seized. The technician pulls the appliance down to four inches of mercury vacuum but cannot tell what percentage was recovered. Does this meet 40 CFR 82.156(b)?

    • A. No, because only the 80 percent level can be used when the compressor has failed
    • B. No, because the technician must document 90 percent recovery
    • C. Yes, because evacuating to four inches of mercury vacuum is an alternative to the recovery percentages
    • D. No, because small appliances must be evacuated to 0 psig
    Show answer

    Answer: C. Yes, because evacuating to four inches of mercury vacuum is an alternative to the recovery percentages

    The small appliance rule lists the recovery percentages and then, as another option, "Evacuate the appliance to four inches of mercury vacuum." Because the options are joined by "or," reaching four inches satisfies the rule without proving a percentage.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  3. 20. When do the small appliance recovery requirements in 40 CFR 82.156(b) apply?

    • A. Only when the appliance is disposed of
    • B. Before opening a small appliance or when disposing of a small appliance
    • C. Only when the recovered refrigerant will be sold
    • D. Only when the appliance's compressor has failed
    Show answer

    Answer: B. Before opening a small appliance or when disposing of a small appliance

    Paragraph (b) begins: "Before opening a small appliance or when disposing of a small appliance, persons must recover refrigerant." It covers both service and disposal, whatever the compressor's condition or what happens to the refrigerant.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  4. 21. Table 1 in 40 CFR 82.156 sets required evacuation levels in inches of mercury vacuum. How does it treat small appliances?

    • A. It applies to small appliances that hold more than 2 pounds
    • B. Small appliances use the very high-pressure row
    • C. Small appliances use the low-pressure row
    • D. It excludes them; small appliances follow the separate requirements in paragraph (b)
    Show answer

    Answer: D. It excludes them; small appliances follow the separate requirements in paragraph (b)

    Table 1 is titled "REQUIRED LEVELS OF EVACUATION FOR APPLIANCES" with the note "[EXCEPT FOR SMALL APPLIANCES, MVACS, AND MVAC-LIKE APPLIANCES]". Small appliances instead follow paragraph (b), which uses recovery percentages or a four-inch vacuum.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  5. 22. Before opening a small appliance, what kind of recovery equipment must you use?

    • A. Any recovery machine, as long as the technician is certified
    • B. A recovery and/or recycling machine certified under 40 CFR 82.158
    • C. Uncertified equipment, if the refrigerant will later be reclaimed
    • D. Uncertified equipment, if the appliance will be disposed of
    Show answer

    Answer: B. A recovery and/or recycling machine certified under 40 CFR 82.158

    Before opening or disposing of a small appliance, persons must recover refrigerant "using a recovery and/or recycling machine certified pursuant to § 82.158." Technician certification, later reclamation or disposal does not replace the equipment certification requirement.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  6. 23. A technician wants to use certified system-dependent recovery equipment on a household refrigerator that holds 6 ounces of refrigerant. What does the charge limit in 40 CFR 82.156(e) mean for this job?

    • A. It may be used, because the limit only bars appliances with a full charge of more than 15 pounds
    • B. It may be used only if the refrigerator's compressor is working
    • C. System-dependent equipment may not be used on any small appliance
    • D. Only a Universal technician may use it
    Show answer

    Answer: A. It may be used, because the limit only bars appliances with a full charge of more than 15 pounds

    System-dependent equipment "may not be used with appliances with a full charge of more than 15 pounds of refrigerant," unless it is permanently attached as a pump-out unit. A 6-ounce refrigerator is far below that limit, and the paragraph sets no compressor or certification-type condition.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  7. 24. Under 40 CFR 82.156(h), recovered refrigerant may in some cases be returned to an appliance without being recycled or reclaimed. Which appliances are left out of that allowance?

    • A. Window air conditioners
    • B. Small appliances
    • C. Household refrigerators
    • D. MVACs and MVAC-like appliances
    Show answer

    Answer: D. MVACs and MVAC-like appliances

    Refrigerant may be returned this way "unless the appliance is an MVAC or MVAC-like appliance." Small appliances such as household refrigerators and window units are not excluded.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  8. 25. Which refrigerant, when used in household refrigerators and freezers, is listed as exempt from the venting prohibition and the requirements of Subpart F?

    • A. Isobutane (R-600a)
    • B. CFC-12
    • C. HFC-134a
    • D. HCFC-22
    Show answer

    Answer: A. Isobutane (R-600a)

    The exempt list includes "Isobutane (R-600a) in retail food refrigerators and freezers (stand-alone units only); household refrigerators, freezers, and combination refrigerators and freezers; and vending machines." HFC-134a is not on the exempt list, so it is a non-exempt substitute, and CFC-12 and HCFC-22 are ozone-depleting refrigerants covered by the rule.

    Source: eCFR: 40 CFR 82.154, Prohibitions (as of Nov 3, 2026)

  9. 26. Propane (R-290) is exempt from the venting prohibition and the requirements of Subpart F in certain end-uses. Which of these end-uses is on that list?

    • A. Motor vehicle air conditioners
    • B. Comfort-cooling chillers
    • C. MVAC-like appliances
    • D. Water coolers
    Show answer

    Answer: D. Water coolers

    The propane exemption covers end-uses including vending machines, "self-contained commercial ice machines, very low temperature refrigeration equipment, and water coolers." Motor vehicle air conditioners, MVAC-like appliances and chillers are not in the propane list.

    Source: eCFR: 40 CFR 82.154, Prohibitions (as of Nov 3, 2026)

  10. 27. A recovery machine made in 1992 and certified under 40 CFR 82.158 is used on a household freezer charged with HFC-134a whose compressor works. The technician will recover a set share of the charge rather than evacuate the freezer to four inches of mercury vacuum. How much of the refrigerant must be recovered under 40 CFR 82.156(b)?

    • A. 70 percent, because the compressor in the appliance is functioning
    • B. 50 percent, because the machine was made before November 15, 1993
    • C. 80 percent of the refrigerant in the small appliance
    • D. No set amount, because machines built before 1993 are exempt from the recovery requirement
    Show answer

    Answer: C. 80 percent of the refrigerant in the small appliance

    When using recovery equipment manufactured before November 15, 1993, the rule says to "recover 80 percent of the refrigerant in the small appliance," with no condition about the compressor. The only other choice it gives is to "Evacuate the appliance to four inches of mercury vacuum"; it sets no lower percentage and no exemption for older machines.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

Disposal

  1. 28. Under the safe disposal rule, when has the refrigerant in an appliance "leaked out"?

    • A. When it escaped because of a system failure, an accident or another unavoidable occurrence not caused by negligence
    • B. When a technician released it while removing the compressor
    • C. When someone deliberately cut the refrigerant lines
    • D. When the appliance sat unused for more than a year
    Show answer

    Answer: A. When it escaped because of a system failure, an accident or another unavoidable occurrence not caused by negligence

    "Leaked out" means the refrigerant escaped "because of system failures, accidents, or other unavoidable occurrences not caused by a person's negligence or deliberate acts such as cutting refrigerant lines." If all the refrigerant leaked out, the final processor must get a signed statement saying so and that recovery is not possible.

    Source: eCFR: 40 CFR 82.155, Safe disposal of appliances (as of Nov 3, 2026)

  2. 29. A landfill operator is the final processor for a delivered dehumidifier (a small appliance) that may still hold refrigerant. The operator chooses to recover the remaining refrigerant itself instead of relying on a signed statement. Which requirement must that recovery follow?

    • A. The Table 1 evacuation levels in 40 CFR 82.156(a)
    • B. None, because a final processor is not a technician
    • C. The small appliance requirements in 40 CFR 82.156(b), using recovery equipment that meets 40 CFR 82.158(e)
    • D. Whatever level the landfill's own written procedure sets
    Show answer

    Answer: C. The small appliance requirements in 40 CFR 82.156(b), using recovery equipment that meets 40 CFR 82.158(e)

    The final processor may "Recover any remaining refrigerant from the appliance in accordance with paragraph (a) of this section," and paragraph (a) requires evacuation "to the levels in § 82.156(b) through (d) using recovery equipment that meets the standards in § 82.158(e) through (g)" as applicable. For a small appliance that means 82.156(b) and 82.158(e); Table 1 excludes small appliances.

    Source: eCFR: 40 CFR 82.155, Safe disposal of appliances (as of Nov 3, 2026)

  3. 30. A final processor verifies recovery with a signed statement instead of recovering the refrigerant itself. What must the statement or contract verify?

    • A. That the appliance was serviced within the last year
    • B. That all refrigerant that had not leaked previously has been recovered from the appliance or shipment
    • C. That the appliance contains no compressor oil
    • D. That the refrigerant was reclaimed to appendix A specifications
    Show answer

    Answer: B. That all refrigerant that had not leaked previously has been recovered from the appliance or shipment

    The final processor may "Verify using a signed statement or a contract that all refrigerant that had not leaked previously has been recovered from the appliance or shipment of appliances." Service history, reclamation or oil content is not what the statement verifies.

    Source: eCFR: 40 CFR 82.155, Safe disposal of appliances (as of Nov 3, 2026)

  4. 31. How long must the final processor of a small appliance keep the signed statements or contracts it obtains?

    • A. One year, on site
    • B. Three years, on site
    • C. Until the appliance is scrapped
    • D. They do not need to be kept
    Show answer

    Answer: B. Three years, on site

    The final processor must keep a copy of all signed statements or contracts on site, in hard copy or electronic format, "for three years." Discarding them right away or keeping them for only one year would not meet this rule.

    Source: eCFR: 40 CFR 82.155, Safe disposal of appliances (as of Nov 3, 2026)

  5. 32. A final processor uses a signed contract with a supplier of small appliances instead of signed statements. What must the contract do?

    • A. List the weight of refrigerant in each appliance
    • B. Be filed with EPA within 30 days
    • C. Name the testing organization that certified the recovery machine
    • D. State that the supplier will recover any remaining refrigerant before delivery, or verify that the refrigerant was properly recovered before the supplier received the appliances
    Show answer

    Answer: D. State that the supplier will recover any remaining refrigerant before delivery, or verify that the refrigerant was properly recovered before the supplier received the appliances

    A signed contract "must either state that the supplier will recover any remaining refrigerant" before delivery "or verify that the refrigerant had been properly recovered prior to receipt by the supplier." The rule does not require refrigerant weights, a filing with EPA or the name of a testing organization.

    Source: eCFR: 40 CFR 82.155, Safe disposal of appliances (as of Nov 3, 2026)

  6. 33. When is it a violation for a final processor to accept a signed statement or contract about refrigerant recovery?

    • A. When the final processor knew or had reason to know the statement or contract is false
    • B. Whenever the supplier is not a certified technician
    • C. Whenever the statement is kept in electronic format
    • D. Whenever the appliance was delivered by a third party
    Show answer

    Answer: A. When the final processor knew or had reason to know the statement or contract is false

    It is a violation to accept a signed statement or contract "if the person receiving the statement or contract knew or had reason to know that the signed statement or contract is false." The rule does not tie the violation to who delivered the appliance or whether the supplier is certified, and it allows the statements to be kept "in hard copy or in electronic format."

    Source: eCFR: 40 CFR 82.155, Safe disposal of appliances (as of Nov 3, 2026)

  7. 34. A recycling center disposes of old window air conditioners that contain a class II refrigerant. It does not service any appliances. Does Subpart F apply to it?

    • A. No, because Subpart F applies only to persons who maintain, service, or repair appliances
    • B. Only if the center also sells refrigerant
    • C. Yes, because Subpart F also applies to persons disposing of such appliances, including small appliances
    • D. Only if the units each hold more than five pounds of refrigerant
    Show answer

    Answer: C. Yes, because Subpart F also applies to persons disposing of such appliances, including small appliances

    Subpart F "also applies to persons disposing of such appliances (including small appliances and motor vehicle air conditioners)".

    Source: eCFR: 40 CFR 82.150, Purpose and scope (as of Nov 3, 2026)

  8. 35. A scrap yard is the final processor for household refrigerators. Its regular commercial suppliers have signed contracts promising to recover the refrigerant before delivery. An individual who drops off one old refrigerator offers to sign the same contract. What does EPA's safe disposal page say about the contract option?

    • A. It frees the scrap yard from notifying its suppliers that refrigerant must be recovered before delivery
    • B. It is meant for transactions between businesses and is not appropriate for infrequent suppliers such as individuals
    • C. It is required for individuals, while signed statements are for commercial suppliers
    • D. It lets the scrap yard accept the refrigerator with no verification at all
    Show answer

    Answer: B. It is meant for transactions between businesses and is not appropriate for infrequent suppliers such as individuals

    EPA says "This contract option is intended to help streamline transactions between businesses and is not appropriate for use with infrequent suppliers," naming individuals and peddlers. For them, the final disposer obtains a signed statement with "the name and address of the person who recovered the refrigerant, and the date that the refrigerant was recovered."

    Source: EPA: Stationary Refrigeration Safe Disposal Requirements

Technician certification

  1. 36. A technician's Section 608 certificate is revoked. What must the technician do before maintaining, servicing, repairing or disposing of any appliances again?

    • A. Recertify
    • B. Pay a fine to the certifying program
    • C. Wait 12 months and then resume work
    • D. Nothing; revocation only cancels the wallet card
    Show answer

    Answer: A. Recertify

    The rule states: "If a technician's certificate is revoked, the technician would need to recertify before maintaining, servicing, repairing, or disposing of any appliances." A waiting period or fine does not restore the right to do the work.

    Source: eCFR: 40 CFR 82.161, Technician certification (as of Nov 3, 2026)

  2. 37. A technician who holds only Type I certification wants to buy a cylinder of a class II refrigerant from a distributor. Under the sales restriction in 40 CFR 82.154(c)(1), does the Type I certification qualify the technician as a buyer?

    • A. No, because only Type II, Type III, or Universal technicians may buy refrigerant
    • B. Yes, because the buyer may be certified as a Type I, Type II, Type III, or Universal technician under 82.161
    • C. No, because buyers must be certified under 40 CFR part 82, subpart B
    • D. Only if the cylinder holds two pounds or less
    Show answer

    Answer: B. Yes, because the buyer may be certified as a Type I, Type II, Type III, or Universal technician under 82.161

    A sale is allowed when "The buyer has been certified as a Type I, Type II, Type III, or Universal technician under § 82.161". The two-pound container provision concerns non-exempt substitute refrigerant "intended for use in an MVAC".

    Source: eCFR: 40 CFR 82.154, Prohibitions (as of Nov 3, 2026)

  3. 38. In 2026, a technician repairs only small appliances charged with a non-exempt substitute refrigerant (no class I or class II refrigerant). Under 40 CFR 82.161, which certification must the technician hold?

    • A. Type I
    • B. None, because the section covers only class I and class II refrigerants
    • C. Type II, because substitute refrigerants fall under Type II
    • D. Certification under 40 CFR part 82, subpart B
    Show answer

    Answer: A. Type I

    "Starting on January 1, 2018, this section applies to technicians and organizations certifying technicians that maintain, service, or repair appliances containing any class I or class II refrigerant or any non-exempt substitute refrigerant." "Persons who maintain, service, or repair small appliances must be certified as Type I technicians."

    Source: eCFR: 40 CFR 82.161, Technician certification (as of Nov 3, 2026)

  4. 39. A certified Type I technician fails to properly use recovery equipment when servicing small appliances. Under 82.161(a)(3), what may result?

    • A. Revocation or suspension of the certificate
    • B. A retest of the recovery equipment model line by its manufacturer
    • C. Conversion of the certificate to an apprentice registration
    • D. A requirement to switch to a mail-in Type I test
    Show answer

    Answer: A. Revocation or suspension of the certificate

    "Failure to demonstrate or failure to properly use the equipment may result in revocation or suspension of the certificate."

    Source: eCFR: 40 CFR 82.161, Technician certification (as of Nov 3, 2026)

  5. 40. A technician takes a closed-book, proctored Type I certification test and scores 76 percent. Under Appendix D, did the technician reach the passing score?

    • A. No, because the passing score for every Type I test is 84 percent
    • B. No, because the passing score is 80 percent
    • C. Yes, because the passing score for the closed-book Type I test is 70 percent
    • D. No, because the passing score is 90 percent
    Show answer

    Answer: C. Yes, because the passing score for the closed-book Type I test is 70 percent

    "The passing score for the closed-book Type I, Type II, Type III and Universal certification test is 70 percent". The 84 percent score applies to "Type I certification tests using the mail-in format".

    Source: eCFR: 40 CFR Part 82, Subpart F, Appendix D (as of Nov 3, 2026)

Recovery techniques

  1. 41. Before recovering refrigerant from a drinking water cooler, a technician compares the refrigerant's pressure with its temperature. For which purposes do EPA's Type I test topics list the use of pressure and temperature?

    • A. To verify that the refrigerant has been reclaimed to the appendix A specifications
    • B. To find the date the appliance was manufactured
    • C. To decide which type of technician certification the job needs
    • D. To identify refrigerants and detect noncondensables
    Show answer

    Answer: D. To identify refrigerants and detect noncondensables

    EPA's Type I recovery-technique topics list the "Use of pressure and temperature to identify refrigerants and detect noncondensables." Reclaimed refrigerant is verified "using the analytical methodology prescribed in section 5 of appendix A of this subpart," not by pressure and temperature readings.

    Source: EPA: Section 608 Technician Certification Test Topics

  2. 42. A dehumidifier charged with HFC-134a has an inoperative compressor, and the technician is recovering its refrigerant with a system-dependent ("passive") recovery device. Which method do EPA's Type I test topics give as an example for this situation?

    • A. Release the remaining refrigerant to the air once the device stops filling
    • B. Heat and sharply strike the compressor
    • C. Put the recovered refrigerant into an empty disposable cylinder
    • D. Open the refrigerant circuit and replace the compressor before recovering
    Show answer

    Answer: B. Heat and sharply strike the compressor

    For small appliances with inoperative compressors, the topics give the example "heat and sharply strike the compressor." Venting is prohibited, disposable cylinders are never refilled, and persons must recover refrigerant "Before opening a small appliance."

    Source: EPA: Section 608 Technician Certification Test Topics

  3. 43. For a small appliance with an inoperative compressor, EPA's Type I test topics list using a vacuum pump as a passive recovery method. What kind of recovery container goes with the vacuum pump in that method?

    • A. A non-pressurized recovery container
    • B. A disposable cylinder that once held new refrigerant
    • C. A sealed cylinder pressurized with nitrogen
    • D. No container, because the vacuum pump exhausts the refrigerant to the air
    Show answer

    Answer: A. A non-pressurized recovery container

    The topics list the method "use a vacuum pump with non-pressurized recovery container." The Core safety topics say to "never refill" disposable cylinders.

    Source: EPA: Section 608 Technician Certification Test Topics

  4. 44. A vending machine charged with HFC-134a has a compressor that has failed. The technician has fitted an access valve on the low side only and is about to begin recovering. According to EPA's Type I test topics, what is still needed?

    • A. Nothing more, because one low side valve is enough when the compressor is inoperative
    • B. Removing the low side valve, because only a high side valve is used
    • C. An access valve on the high side as well, so both sides have one
    • D. Releasing the high side refrigerant to the air before recovery starts
    Show answer

    Answer: C. An access valve on the high side as well, so both sides have one

    EPA's Type I topics list the "Need to install both high and low side access valves when recovering refrigerant from small appliances with inoperative compressors." A low side valve alone falls short of that, and the Core topics list the "Venting prohibition at servicing."

    Source: EPA: Section 608 Technician Certification Test Topics

  5. 45. A household refrigerator charged with HFC-134a still has a working compressor, and the technician is recovering its refrigerant with a system-dependent ("passive") recovery device. What do EPA's Type I test topics say to do with the compressor?

    • A. Keep it switched off for the whole recovery
    • B. Remove it from the refrigerant circuit before recovery starts
    • C. Operate it during the recovery
    • D. Vent the refrigerant from the compressor first
    Show answer

    Answer: C. Operate it during the recovery

    When recovering with a system-dependent (passive) recovery device, the topics list the "Need to operate operative compressors." Removing the compressor first would open the appliance, and persons must recover refrigerant "Before opening a small appliance."

    Source: EPA: Section 608 Technician Certification Test Topics

  6. 46. A technician has finished recovering refrigerant from a window air conditioner and is wrapping up the service call. Which item do EPA's Type I test topics say should be removed at the conclusion of service?

    • A. The appliance's process stub
    • B. The appliance's door gasket
    • C. The solderless access fittings
    • D. The appliance's compressor oil
    Show answer

    Answer: C. The solderless access fittings

    EPA's Type I recovery-technique topics state that the technician "Should remove solderless access fittings at conclusion of service." A process stub, by contrast, is tubing "that can be resealed at the conclusion of repair or service."

    Source: EPA: Section 608 Technician Certification Test Topics

  7. 47. An R-12 household refrigerator is being replaced, and the owner asks which refrigerant has likely taken R-12's place. Which answer matches EPA's Type I test topics?

    • A. R-11
    • B. R-114
    • C. R-113
    • D. R-134a
    Show answer

    Answer: D. R-134a

    The topics list "Hydrofluorocarbon (HFC)-134a (also called R-134a) as likely substitute for chlorofluorocarbon (CFC)-12 (also called R-12)." R-11, R-114 and R-113 are themselves CFCs: "Commercial CFC production began with R-12 in early 1931, R-11 in 1932, R-114 in 1933, and R-113 in 1934."

    Source: EPA: Section 608 Technician Certification Test Topics