53 free practice questions on the Type II section. Each answer is explained and linked to the official source it comes from.

Fact-checked against official sources · Last checked

EPA 608 Type II

53 questions across 9 topics. After each answer you see why it is right, with a link to the official source.

Tip: press A, B, C or D to answer and Enter for the next question. Nothing you answer leaves your browser.

Review all 53 questions

Prefer to read? Here is every question in the EPA 608 Type II set, grouped by topic. Open a question to see the answer, why it is right and the official source.

Definitions

  1. 1. A refrigerant has a liquid phase saturation pressure of 250 psia at 104 °F. Under the definitions, an appliance using it is which kind of appliance?

    • A. Medium-pressure appliance
    • B. Low-pressure appliance
    • C. Very high-pressure appliance
    • D. High-pressure appliance
    Show answer

    Answer: D. High-pressure appliance

    A high-pressure appliance uses a refrigerant with a liquid phase saturation pressure "between 170 psia and 355 psia at 104 °F," and 250 psia falls in that range. Medium-pressure stops at 170 psia, and very high-pressure starts above 355 psia.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  2. 2. One appliance is used partly for industrial process refrigeration and partly for other applications. When is it considered industrial process refrigeration equipment?

    • A. When 50 percent or more of its operating capacity is used for industrial process refrigeration
    • B. Only when all of its capacity serves an industrial process
    • C. Whenever the owner chooses to classify it that way
    • D. Whenever any part of its capacity serves an industrial process
    Show answer

    Answer: A. When 50 percent or more of its operating capacity is used for industrial process refrigeration

    The definition says such an appliance "will be considered industrial process refrigeration equipment if 50 percent or more of its operating capacity is used for industrial process refrigeration." The test is the share of operating capacity, not any use or the owner's choice.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  3. 3. Which appliances does the definition of comfort cooling name as examples?

    • A. Industrial ice machines and ice rinks
    • B. Supermarket display cases and walk-in coolers
    • C. Chillers, commercial split systems, and packaged roof-top units
    • D. Cold storage warehouse refrigeration
    Show answer

    Answer: C. Chillers, commercial split systems, and packaged roof-top units

    The definition says "Comfort cooling appliances include but are not limited to chillers, commercial split systems, and packaged roof-top units." Supermarket and cold storage equipment is commercial refrigeration, and ice machines and ice rinks are industrial process refrigeration.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  4. 4. An appliance uses a refrigerant whose critical temperature is below 104 °F. Under the EPA definitions, which kind of appliance is it?

    • A. Very high-pressure appliance
    • B. Medium-pressure appliance
    • C. High-pressure appliance
    • D. Low-pressure appliance
    Show answer

    Answer: A. Very high-pressure appliance

    A very high-pressure appliance is one that uses a refrigerant "with a critical temperature below 104 °F or with a liquid phase saturation pressure above 355 psia at 104 °F." The high-pressure definition is based only on a saturation pressure between 170 and 355 psia at 104 °F, not on critical temperature.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  5. 5. Under the definitions, what does it mean to retire an appliance?

    • A. Remove the refrigerant and disassemble or impair the refrigerant circuit so the appliance as a whole cannot be used by anyone in the future
    • B. Convert it from one refrigerant to another
    • C. Evacuate it to atmospheric pressure and temporarily shut it down
    • D. Sell it to a new owner
    Show answer

    Answer: A. Remove the refrigerant and disassemble or impair the refrigerant circuit so the appliance as a whole cannot be used by anyone in the future

    Retire means "the removal of the refrigerant and the disassembly or impairment of the refrigerant circuit such that the appliance as a whole is rendered unusable by any person in the future." A temporary shutdown is mothballing, and a refrigerant change is a retrofit.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  6. 6. Under the EPA definition, what does it mean to mothball an appliance?

    • A. Permanently retire it and send it for disposal
    • B. Evacuate its refrigerant to at least atmospheric pressure and temporarily shut it down
    • C. Convert it from one refrigerant to another
    • D. Leave it fully charged and turn off its power
    Show answer

    Answer: B. Evacuate its refrigerant to at least atmospheric pressure and temporarily shut it down

    Mothball means "to evacuate refrigerant from an appliance, or the affected isolated section or component of an appliance, to at least atmospheric pressure, and to temporarily shut down that appliance." Converting to another refrigerant is the definition of a retrofit, and mothballing is temporary, not a retirement.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  7. 7. An owner converts an appliance to a new refrigerant and, to make the system compatible with it, also changes the lubricant, filters, driers and o-rings. How does the definition of retrofit treat those changes?

    • A. They make the work a retirement of the appliance
    • B. They are part of retrofitting the appliance
    • C. They count as mothballing the appliance
    • D. They count as a seasonal variance
    Show answer

    Answer: B. They are part of retrofitting the appliance

    Retrofit means "to convert an appliance from one refrigerant to another refrigerant. Retrofitting includes the conversion of the appliance to achieve system compatibility with the new refrigerant and may include, but is not limited to, changes in lubricants, gaskets, filters, driers, valves, o-rings or appliance components."

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  8. 8. An owner needs the full charge of a high-pressure appliance (full charge of 50 or more pounds of a class I or class II refrigerant). Which of these is one of the four methods the definition of full charge allows?

    • A. Actual measurements of the amount of refrigerant added to or evacuated from the appliance, including for seasonal variances
    • B. The amount printed on the last refrigerant cylinder bought for the appliance
    • C. The total refrigerant bought for the whole facility in the last calendar year
    • D. The largest single refrigerant addition made in the past 12 months
    Show answer

    Answer: A. Actual measurements of the amount of refrigerant added to or evacuated from the appliance, including for seasonal variances

    Full charge is determined "by using one or a combination of the following four methods", one of which is "Use of actual measurements of the amount of refrigerant added to or evacuated from the appliance, including for seasonal variances". The other three are the manufacturer's determination, appropriate calculations, and an established range.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  9. 9. Which pattern of refrigerant removal and addition fits the definition of a seasonal variance?

    • A. Refrigerant is added every summer to make up for a slow leak
    • B. Refrigerant is removed when the season changes, and more than that amount is added back later
    • C. Refrigerant is removed one season and added back 18 months later
    • D. Refrigerant is removed because of a seasonal change in ambient conditions, then an amount less than or equal to it is added back, both within one consecutive 12-month period
    Show answer

    Answer: D. Refrigerant is removed because of a seasonal change in ambient conditions, then an amount less than or equal to it is added back, both within one consecutive 12-month period

    A seasonal variance is "the removal of refrigerant from an appliance due to a change in ambient conditions caused by a change in season, followed by the subsequent addition of an amount that is less than or equal to the amount of refrigerant removed in the prior change in season, where both the removal and addition of refrigerant occurs within one consecutive 12-month period."

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

Evacuation levels

  1. 10. Using recovery equipment made in 2020, a technician must reach 15 inches of Hg vacuum before a major repair on which of these no-leak appliances?

    • A. A high-pressure appliance with a full charge of less than 200 pounds
    • B. A very high-pressure appliance
    • C. A medium-pressure appliance with a full charge of 200 pounds or more
    • D. A low-pressure appliance
    Show answer

    Answer: C. A medium-pressure appliance with a full charge of 200 pounds or more

    For equipment made on or after November 15, 1993, Table 1 lists 15 inches only for a medium-pressure appliance with a full charge "of 200 pounds or more of refrigerant." Very high-pressure appliances and high-pressure appliances under 200 pounds are at 0 inches, and low-pressure appliances at 25 mm Hg absolute.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  2. 11. For which of these appliances does Table 1 in 40 CFR 82.156 set the same evacuation level whether the recovery equipment was made before or after November 15, 1993?

    • A. A high-pressure appliance with a full charge of 200 pounds or more
    • B. A very high-pressure appliance
    • C. A medium-pressure appliance with a full charge of less than 200 pounds
    • D. A medium-pressure appliance with a full charge of 200 pounds or more
    Show answer

    Answer: B. A very high-pressure appliance

    Table 1 gives "Very high-pressure appliance" 0 inches of Hg vacuum in both equipment columns. The other three options move from 4 inches for older equipment to 10 or 15 inches for newer equipment.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  3. 12. Before a major repair on a no-leak medium-pressure appliance with a 150-pound full charge, a technician's recovery machine made in 2010 reaches 10 inches of Hg vacuum. Under Table 1, is that enough?

    • A. No, 15 inches of Hg vacuum is required
    • B. Yes, 10 inches is the level for this appliance with equipment made on or after November 15, 1993
    • C. No, 25 mm Hg absolute is required
    • D. No, 29 inches of Hg vacuum is required
    Show answer

    Answer: B. Yes, 10 inches is the level for this appliance with equipment made on or after November 15, 1993

    Table 1 lists a medium-pressure appliance "with a full charge of less than 200 pounds of refrigerant" at 10 inches for equipment made on or after November 15, 1993. The 15-inch level is for medium-pressure appliances of 200 pounds or more, and 25 mm Hg absolute is for low-pressure appliances.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  4. 13. A technician recovers refrigerant from the air conditioner of a construction loader (an MVAC-like appliance) before the machine is scrapped. To which pressure level does 40 CFR 82.156(c) allow the technician to reduce the system?

    • A. Reaching 0 psig
    • B. Reaching 10 inches of Hg vacuum
    • C. Reducing the system pressure to or below 102 mm of mercury vacuum
    • D. Reaching 25 mm Hg absolute
    Show answer

    Answer: C. Reducing the system pressure to or below 102 mm of mercury vacuum

    Persons recovering refrigerant from MVAC-like appliances for disposal must follow subpart B "or reduce the system pressure to or below 102 mm of mercury vacuum." Table 1 levels do not apply to MVAC-like appliances.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

Recovery practices

  1. 14. A technician evacuates refrigerant from appliances with a full charge of more than 5 and less than 50 pounds so they can be disposed of. Which item must the technician's records include for each appliance?

    • A. The appliance owner's phone number
    • B. The appliance's serial number and purchase price
    • C. The company name, location of the appliance, date of recovery, and type of refrigerant recovered
    • D. A photograph of the empty appliance
    Show answer

    Answer: C. The company name, location of the appliance, date of recovery, and type of refrigerant recovered

    For these disposals, technicians must keep records for three years documenting "The company name, location of the appliance, date of recovery, and type of refrigerant recovered for each appliance," plus monthly totals and transfers for reclamation or destruction. Serial numbers, prices, phone numbers and photographs are not listed.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  2. 15. A technician may evacuate only the part of an appliance being serviced, instead of the whole appliance, if the refrigerant in that part can be isolated to what?

    • A. A disposable refrigerant cylinder
    • B. A system receiver
    • C. The recovery machine's filter-drier
    • D. The appliance's suction line
    Show answer

    Answer: B. A system receiver

    The rule lets technicians evacuate either the entire appliance or the part to be serviced, "if the refrigerant in the part can be isolated to a system receiver." A system receiver is defined as the isolated portion or vessel of the appliance used to hold the charge during service.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  3. 16. Recovery and/or recycling equipment certified under 40 CFR 82.158(d), for use on appliances such as high-pressure systems, must have what on all hoses?

    • A. Low-loss fittings
    • B. Open-ended quick connectors
    • C. Flare fittings
    • D. Process stubs
    Show answer

    Answer: A. Low-loss fittings

    The equipment standard states: "The equipment must be equipped with low-loss fittings on all hoses." A low-loss fitting closes automatically or manually when disconnected, which limits refrigerant release from hoses.

    Source: eCFR: 40 CFR 82.158, Standards for recovery and/or recycling equipment (as of Nov 3, 2026)

  4. 17. Leaks in a high-pressure appliance make the Table 1 levels unattainable. Its leaking and non-leaking components have been isolated from each other. To what level must the non-leaking components to be opened be evacuated?

    • A. No evacuation is required
    • B. No higher than 0 psig
    • C. No higher than 5 psig
    • D. The levels specified in Table 1
    Show answer

    Answer: D. The levels specified in Table 1

    In this case the rule says to "Evacuate non-leaking components to be opened or disposed of to the levels specified in Table 1." The 0 psig limit is the ceiling for the leaking components only.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  5. 18. A company services only appliances that it owns, and all of them contain pump-out units. Which requirement of 40 CFR 82.156 is the company exempt from?

    • A. Evacuating the appliances to the Table 1 levels
    • B. Having its technicians certified as Type II technicians
    • C. Recovering refrigerant before opening the appliances
    • D. Using certified, self-contained recovery and/or recycling equipment
    Show answer

    Answer: D. Using certified, self-contained recovery and/or recycling equipment

    Persons who service "only appliances that they own and that contain pump-out units are exempt from the requirement to use certified, self-contained recovery and/or recycling equipment." The exemption covers only that equipment requirement, not evacuation levels, recovery before opening, or technician certification.

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  6. 19. A certified technician will open the air-conditioning system of a farm tractor, an MVAC-like appliance. Which equipment does 40 CFR 82.156(c) require the technician to be properly using?

    • A. Any recovery machine that reaches the Table 1 level for high-pressure appliances
    • B. Recovery and/or recycling equipment certified pursuant to § 82.158(f) or § 82.36, as applicable
    • C. Small-appliance recovery equipment certified under appendix C
    • D. System-dependent recovery equipment of any kind
    Show answer

    Answer: B. Recovery and/or recycling equipment certified pursuant to § 82.158(f) or § 82.36, as applicable

    The rule says "Persons may only open MVAC-like appliances while properly using, as defined at § 82.32(e), recovery and/or recycling equipment certified pursuant to § 82.158(f) or § 82.36, as applicable."

    Source: eCFR: 40 CFR 82.156, Proper evacuation of refrigerant from appliances (as of Nov 3, 2026)

  7. 20. A technician connects a recovery machine to a high-pressure appliance that holds a large charge. According to EPA's Type 2 test topics, what at the beginning of the job speeds up recovery?

    • A. Recovering vapor first and leaving the liquid for last
    • B. Recovering liquid at the beginning of the recovery process
    • C. Briefly opening the system to the atmosphere to lower its pressure
    • D. Running the recovery machine with its outlet valve closed
    Show answer

    Answer: B. Recovering liquid at the beginning of the recovery process

    EPA's Type 2 recovery technique topics state: "Recovering liquid at beginning of recovery process speeds up process".

    Source: EPA: Section 608 Technician Certification Test Topics

  8. 21. A recovery from a high-pressure appliance is running slower than the technician would like. Which combination of temperature changes do EPA's Type 2 test topics list as methods for speeding recovery?

    • A. Heat the recovery vessel, and chill the appliance the refrigerant is being recovered from
    • B. Heat both the recovery vessel and the appliance
    • C. Chill the recovery vessel, and heat the appliance the refrigerant is being recovered from
    • D. Chill both the recovery vessel and the appliance
    Show answer

    Answer: C. Chill the recovery vessel, and heat the appliance the refrigerant is being recovered from

    EPA's Type 2 topics list "Other methods for speeding recovery (chilling recovery vessel, heating appliance or vessel from which refrigerant is being recovered)". The vessel that receives the refrigerant is chilled and the source is heated, not the other way around.

    Source: EPA: Section 608 Technician Certification Test Topics

  9. 22. A recovery machine has just pulled a high-pressure appliance down to the required recovery vacuum. Why do EPA's Type 2 test topics say to wait a few minutes before finishing?

    • A. To see if system pressure rises, which would indicate liquid refrigerant still in the system or in the oil
    • B. To let non-condensables vent to the atmosphere
    • C. To let the gauges return to zero before disconnecting
    • D. To let the recovery cylinder warm up so it can be filled further
    Show answer

    Answer: A. To see if system pressure rises, which would indicate liquid refrigerant still in the system or in the oil

    EPA's Type 2 topics list the "Need to wait a few minutes after reaching required recovery vacuum to see if system pressure rises (indicating that there is still liquid refrigerant in the system or in the oil)".

    Source: EPA: Section 608 Technician Certification Test Topics

Leak repair

  1. 23. As of April 10, 2020, the appliance maintenance and leak repair rules in 40 CFR 82.157 apply to which appliances?

    • A. Appliances with a full charge of 50 or more pounds of any refrigerant, including substitutes alone
    • B. All high-pressure appliances, regardless of charge size
    • C. Appliances with a full charge of more than 15 pounds of any refrigerant
    • D. Appliances with a full charge of 50 or more pounds of a class I or class II refrigerant, or a blend containing one
    Show answer

    Answer: D. Appliances with a full charge of 50 or more pounds of a class I or class II refrigerant, or a blend containing one

    As of April 10, 2020, the section applies only to appliances with a full charge of 50 or more pounds of a class I or class II refrigerant or a blend containing one. It states the requirements "do not apply to appliances containing solely substitute refrigerants."

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  2. 24. Under 40 CFR 82.157(c)(2), the 10 percent leak rate applies to comfort cooling appliances and to which other appliances?

    • A. All commercial refrigeration equipment
    • B. All industrial process refrigeration equipment
    • C. Other appliances with a full charge of 50 or more pounds that are not commercial refrigeration or industrial process refrigeration
    • D. Small appliances
    Show answer

    Answer: C. Other appliances with a full charge of 50 or more pounds that are not commercial refrigeration or industrial process refrigeration

    The rule sets a "10 percent leak rate for comfort cooling appliances or other appliances with a full charge of 50 or more pounds of refrigerant not covered by (c)(2)(i) or (ii) of this section." Paragraphs (i) and (ii) cover commercial refrigeration and industrial process refrigeration, which have their own rates.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  3. 25. A supermarket's display case system has a full charge of 50 or more pounds of a class II refrigerant. Which leak-rate category in 40 CFR 82.157 does it fall into?

    • A. Commercial refrigeration
    • B. Comfort cooling
    • C. Industrial process refrigeration
    • D. It is not covered by any leak-rate category
    Show answer

    Answer: A. Commercial refrigeration

    Commercial refrigeration covers the retail food and cold storage sectors, and "Retail food appliances include the refrigeration equipment found in supermarkets." Section 82.157 sets a "20 percent leak rate for commercial refrigeration equipment."

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  4. 26. An owner chooses to repair an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant) but fails to bring the leak rate below the applicable rate. What must the owner then do?

    • A. Pay a fixed penalty to EPA and keep operating
    • B. Create and implement a retrofit or retirement plan
    • C. Report the appliance to the state fire marshal
    • D. Nothing more, because a repair was attempted
    Show answer

    Answer: B. Create and implement a retrofit or retirement plan

    The rule says that if the owner or operator "elects to repair leaks, but fails to bring the leak rate below the applicable leak rate, the owner or operator must create and implement a retrofit or retirement plan." Attempting a repair does not end the obligation.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  5. 27. For an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant), when must the owner or operator calculate the leak rate?

    • A. Every time refrigerant is added, except right after a retrofit or new installation, or for a seasonal variance
    • B. Only once per calendar year
    • C. Only when a leak inspection finds a leak
    • D. Only when the appliance is disposed of
    Show answer

    Answer: A. Every time refrigerant is added, except right after a retrofit or new installation, or for a seasonal variance

    The owner or operator "must calculate the leak rate every time refrigerant is added to an appliance" unless the addition follows a retrofit or new installation, or qualifies as a seasonal variance. The rule ties the calculation to each refrigerant addition, not to a yearly schedule or to inspection results.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  6. 28. Leaks were repaired on an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant). The leaks are presumed repaired if there is no further refrigerant addition for how long after the repair?

    • A. 10 days
    • B. 30 days
    • C. 3 months
    • D. 12 months
    Show answer

    Answer: D. 12 months

    The rule says the leaks "will be presumed to be repaired if there is no further refrigerant addition for 12 months after the repair" or if the required leak inspections find no leaks. The 10- and 30-day periods are deadlines for verification tests and repairs, not the presumption period.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  7. 29. An appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant) is over its leak rate. The only reason the repair needs more time is that replacement components are not available within 30 days. No industrial process shutdown is required, and the owner or operator meets the documentation and EPA request requirements for an extension. What is the latest the repair time can run, counted from the date the appliance exceeded the leak rate?

    • A. 120 days
    • B. 180 days
    • C. 270 days
    • D. 365 days
    Show answer

    Answer: B. 180 days

    Extra time is allowed "up to 30 days after receiving delivery of the necessary components, not to exceed 180 days (or 270 days if an industrial process shutdown is required)" from the date the leak rate was exceeded. The 270-day cap applies only when an industrial process shutdown is required.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  8. 30. An appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant) is mothballed during its repair period. When do the repair time frames start running again?

    • A. On the day additional refrigerant is added to the appliance (or the isolated leaking component)
    • B. On the day the appliance is mothballed
    • C. 12 months after the appliance is mothballed
    • D. When EPA sends written approval
    Show answer

    Answer: A. On the day additional refrigerant is added to the appliance (or the isolated leaking component)

    The time frames "are temporarily suspended when an appliance is mothballed" and "will resume on the day additional refrigerant is added to the appliance" (or component, if the leaking component was isolated). Mothballing stops the clock, so it does not restart on the day of mothballing.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  9. 31. The owner of an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant) writes a retrofit or retirement plan. What is the longest schedule for completing the work that the plan may set?

    • A. 30 days
    • B. 90 days
    • C. One year
    • D. Five years
    Show answer

    Answer: C. One year

    A retrofit or retirement plan must contain "A schedule, not to exceed one-year, for completion of the appliance retrofit or retirement." The 30-day period is the deadline for creating the plan, not for finishing the work.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  10. 32. An appliance with 50 pounds or more of a class I or class II refrigerant leaked 125 percent or more of its full charge this calendar year. What deadline does 40 CFR 82.157 set for the owner or operator to submit a report to EPA?

    • A. December 31 of the same year
    • B. January 30 of the next year
    • C. July 30 of the next year
    • D. March 1 of the next year
    Show answer

    Answer: D. March 1 of the next year

    For chronically leaking appliances, the report "must be submitted by March 1 of the subsequent year" and describe efforts to find and repair the leaks. January 30 and July 30 are the dates for certifying programs' activity reports under appendix D, not for this report.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  11. 33. An owner uses the annualizing method to calculate the leak rate of a high-pressure appliance (full charge of 50 or more pounds of a class I or class II refrigerant). Which number of days does the method divide by 365 days?

    • A. Always 365 days
    • B. The number of days since the appliance was installed
    • C. The shorter of the number of days since the last day refrigerant was added or 365 days
    • D. The number of days since the last leak inspection
    Show answer

    Answer: C. The shorter of the number of days since the last day refrigerant was added or 365 days

    Step 2 is to "Take the shorter of the number of days that have passed since the last day refrigerant was added or 365 days and divide that number by 365 days". Step 3 then divides the Step 1 result by this number.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

Verification and inspections

  1. 34. A leak was repaired without evacuating an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant). Within how many days of the successful initial verification test must the follow-up verification test be done?

    • A. 30 days
    • B. 120 days
    • C. 12 months
    • D. 10 days
    Show answer

    Answer: D. 10 days

    A follow-up verification test "must be performed within 10 days of the successful initial verification test." When the appliance was evacuated for the repair, the 10 days can instead run from when it reaches normal operating characteristics and conditions.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  2. 35. A leak repair on an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant) required evacuating part of the appliance. When must the initial verification test be performed?

    • A. Before adding any refrigerant to the appliance
    • B. After the appliance has run at normal conditions for 30 days
    • C. Only after the next refrigerant addition
    • D. Within 12 months of the repair
    Show answer

    Answer: A. Before adding any refrigerant to the appliance

    For repairs that require evacuating the appliance or a portion of it, the initial verification test "must be performed before adding any refrigerant to the appliance." The rule defines the initial test as one done before refrigerant is added back.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  3. 36. A commercial refrigeration appliance with a full charge of 500 or more pounds of a class I or class II refrigerant has exceeded its allowed leak rate. It has no automatic leak detection system. What leak inspection schedule does 40 CFR 82.157 set for it?

    • A. Once per calendar year
    • B. Once every two years
    • C. Once every five years
    • D. Once every three months
    Show answer

    Answer: D. Once every three months

    For commercial refrigeration and industrial process refrigeration appliances of 500 or more pounds, leak inspections are required "once every three months" until four quarters in a row show no leaking above the applicable rate. Once per calendar year applies to the 50-to-under-500-pound size and to comfort cooling appliances.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  4. 37. Under 40 CFR 82.157 (appliances with a full charge of 50 or more pounds of a class I or class II refrigerant), who must conduct the required leak inspections?

    • A. An EPA inspector
    • B. Any employee of the owner or operator, whether or not certified
    • C. A certified technician
    • D. The appliance manufacturer
    Show answer

    Answer: C. A certified technician

    The rule says "Leak inspections must be conducted by a certified technician using method(s) determined by the technician to be appropriate for that appliance." An uncertified employee does not meet this requirement.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  5. 38. An automatic leak detection system that directly detects refrigerant in air is used on an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant). What refrigerant concentration does the rule set as the level at which it must alert the owner or operator?

    • A. 10 parts per million
    • B. 500 parts per million
    • C. 100 parts per million
    • D. 1,000 parts per million
    Show answer

    Answer: C. 100 parts per million

    The system must "Alert the owner or operator when a refrigerant concentration of 100 parts per million of vapor" of the refrigerant is reached. The 10 parts per million figure is the level it must be able to detect accurately, not the alert level.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  6. 39. An automatic leak detection system on an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant) monitors the appliance's conditions instead of detecting refrigerant in air. When must it alert the owner or operator?

    • A. When measurements indicate a loss of 50 pounds of refrigerant or 10 percent of the full charge, whichever is more
    • B. When measurements indicate a loss of 50 pounds of refrigerant or 10 percent of the full charge, whichever is less
    • C. Only when a technician next inspects the appliance
    • D. When measurements indicate a loss of 20 percent of the full charge
    Show answer

    Answer: B. When measurements indicate a loss of 50 pounds of refrigerant or 10 percent of the full charge, whichever is less

    Such a system "must automatically alert the owner or operator when measurements indicate a loss of 50 pounds of refrigerant or 10 percent of the full charge, whichever is less." The rule uses whichever of the two amounts is less, not whichever is more.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  7. 40. A standing pressure decay test shows that an appliance is leaking but not where. Under the definition of leak inspection, what must such a method be used together with?

    • A. A second standing pressure decay test
    • B. A charging chart
    • C. A sight glass check
    • D. Methods that can determine the location of a leak
    Show answer

    Answer: D. Methods that can determine the location of a leak

    Methods that show whether an appliance is leaking but not where "must be used in conjunction with methods that can determine the location of a leak." Charging charts and sight glass checks are themselves listed as methods that do not find the location.

    Source: eCFR: 40 CFR 82.152, Definitions (as of Nov 3, 2026)

  8. 41. After a leak repair on an appliance covered by 40 CFR 82.157 (full charge of 50 or more pounds of a class I or class II refrigerant), it is unsafe to be present while the system runs at normal operating characteristics and conditions. When must the follow-up verification test be done?

    • A. Only after the system has run at normal operating characteristics and conditions for 30 days
    • B. Where practicable, before the system returns to normal operating characteristics and conditions
    • C. Within 12 months of the repair
    • D. Only after the next refrigerant addition
    Show answer

    Answer: B. Where practicable, before the system returns to normal operating characteristics and conditions

    Where it is unsafe or impossible to test at normal conditions, "the verification test must, where practicable, be conducted prior to the system returning to normal operating characteristics and conditions." The test moves earlier, before the system returns to normal conditions, not later.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  9. 42. A commercial refrigeration appliance (full charge of 50 or more pounds of a class I or class II refrigerant) has exceeded its leak rate. An automatic leak detection system monitors only part of the appliance. What applies to the rest of the appliance?

    • A. It is exempt from leak inspections because part of the appliance is monitored
    • B. It continues to be subject to any applicable leak inspection requirements
    • C. It needs a leak inspection only once every five years
    • D. It must be retired within one year
    Show answer

    Answer: B. It continues to be subject to any applicable leak inspection requirements

    When the system monitors only portions of an appliance, "the remainder of the appliance continues to be subject to any applicable leak inspection requirements." The exemption from quarterly or annual inspections covers only portions "continuously monitored by an automatic leak detection system that is audited or calibrated annually."

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  10. 43. On a high-pressure appliance (full charge of 50 or more pounds of a class I or class II refrigerant), the initial verification test shows that a leak repair was not successful. What does 40 CFR 82.157 allow the owner or operator to do?

    • A. Conduct as many additional repairs and initial verification tests as needed within the applicable time period
    • B. Wait 12 months before trying another repair
    • C. Nothing more; the appliance must be retired the same day
    • D. Skip the follow-up verification test for that leak
    Show answer

    Answer: A. Conduct as many additional repairs and initial verification tests as needed within the applicable time period

    If the initial test shows the repairs failed, the owner or operator "may conduct as many additional repairs and initial verification tests as needed within the applicable time period." The rule does not require same-day retirement, and both initial and follow-up tests are still required for each repaired leak.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  11. 44. An automatic leak detection system that directly detects refrigerant in air replaces the leak inspections on a high-pressure appliance covered by 40 CFR 82.157. Where must its sensors or intakes be placed?

    • A. Only at the building's fresh-air intake
    • B. Only beside the refrigerant storage cylinders
    • C. So they continuously monitor refrigerant concentrations in air in proximity to the compressor, evaporator, condenser, and other areas with a high potential for a refrigerant leak
    • D. Anywhere in the building, as long as at least one sensor is used
    Show answer

    Answer: C. So they continuously monitor refrigerant concentrations in air in proximity to the compressor, evaporator, condenser, and other areas with a high potential for a refrigerant leak

    Such a system must "Have sensors or intakes placed so that they will continuously monitor the refrigerant concentrations in air in proximity to the compressor, evaporator, condenser, and other areas with a high potential for a refrigerant leak".

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

Records and certification

  1. 45. For an appliance with a full charge of 50 or more pounds of a class I or class II refrigerant, how long must the owner or operator keep the records of its full charge and how it was determined?

    • A. One year after the appliance is installed
    • B. Until the next leak inspection
    • C. Five years after the appliance is installed
    • D. Until three years after the appliance is retired
    Show answer

    Answer: D. Until three years after the appliance is retired

    Owners or operators must determine the full charge and keep that information "for each appliance until three years after the appliance is retired." This is longer than the three-year default that applies to most other records in the section.

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

  2. 46. A technician performs initial and follow-up verification tests on repaired leaks in a high-pressure appliance (full charge of 50 or more pounds of a class I or class II refrigerant). Which items must the owner's verification test records include?

    • A. Only the date of the follow-up test
    • B. The location(s) of all repaired leaks that were tested, the type(s) of verification test(s) used, and the results of those tests
    • C. The cost of each repair
    • D. The technician's certification exam score
    Show answer

    Answer: B. The location(s) of all repaired leaks that were tested, the type(s) of verification test(s) used, and the results of those tests

    Records "must include the location of the appliance, the date(s) of the verification tests, the location(s) of all repaired leaks that were tested, the type(s) of verification test(s) used, and the results of those tests." Technicians conducting the tests must provide that documentation "upon conclusion of that service".

    Source: eCFR: 40 CFR 82.157, Appliance maintenance and leak repair (as of Nov 3, 2026)

Leak detection

  1. 47. A technician suspects that a high-pressure system with a hermetic compressor has been losing refrigerant. Which pair of signs of leakage do EPA's Type 2 test topics name for high-pressure systems?

    • A. Excessive superheat, and traces of oil for hermetics
    • B. Very low superheat, and frost on the compressor shell
    • C. Higher-than-normal discharge pressure, and a clean, dry compressor shell
    • D. A rise in condenser airflow, and faded paint on the cabinet
    Show answer

    Answer: A. Excessive superheat, and traces of oil for hermetics

    EPA's Type 2 leak detection topics list "Signs of leakage in high-pressure systems (excessive superheat, traces of oil for hermetics)". None of the other signs is listed.

    Source: EPA: Section 608 Technician Certification Test Topics

  2. 48. A technician has finished installing a new high-pressure split system and is about to put in its first refrigerant charge. According to EPA's Type 2 test topics, what comes before charging the equipment?

    • A. A leak test
    • B. Running the system for 24 hours on a partial charge
    • C. Releasing a small amount of refrigerant to purge the lines
    • D. Nothing, because leak tests are needed only on equipment that has been repaired
    Show answer

    Answer: A. A leak test

    EPA's Type 2 leak detection topics list the "Need to leak test before charging or recharging equipment". The topic names charging as well as recharging, so it is not limited to repaired equipment.

    Source: EPA: Section 608 Technician Certification Test Topics

  3. 49. A technician will pressurize a high-pressure system to find a leak. Which ranking of leak test gases, from most to least preferred, matches EPA's Type 2 test topics?

    • A. Pure refrigerant, then nitrogen with a trace quantity of R-22, then nitrogen alone
    • B. Nitrogen with a trace quantity of R-22, then pure refrigerant, then nitrogen alone
    • C. Nitrogen with a trace quantity of R-22, then nitrogen alone, then pure refrigerant
    • D. Nitrogen alone, then nitrogen with a trace quantity of R-22, then pure refrigerant
    Show answer

    Answer: D. Nitrogen alone, then nitrogen with a trace quantity of R-22, then pure refrigerant

    EPA's Type 2 topics give the order of preference as "nitrogen alone best, but nitrogen with trace quantity of hydrochlorofluorocarbon (HCFC)-22 (also called R-22) better than pure refrigerant".

    Source: EPA: Section 608 Technician Certification Test Topics

Refrigeration

  1. 50. A standard temperature-pressure chart gives 120 psig for a high-pressure refrigerant at a certain temperature. The technician needs the pressure in psia. Which value is it?

    • A. 105.3 psia
    • B. 120 psia
    • C. 134.7 psia
    • D. 149.9 psia
    Show answer

    Answer: C. 134.7 psia

    EPA's Type 2 topics note the "need to add 14.7 to translate pounds per square inch gauge (psig) to pounds per square inch absolute (psia)". Our calculation: 120 + 14.7 = 134.7 psia.

    Source: EPA: Section 608 Technician Certification Test Topics

  2. 51. A technician is called to a home central air conditioner and needs to know which refrigerant it contains. Where does EPA say most air conditioners identify their refrigerant?

    • A. On a nameplate on the unit
    • B. On the thermostat display
    • C. On the insulation of the refrigerant lines
    • D. On the home's electric meter
    Show answer

    Answer: A. On a nameplate on the unit

    EPA's HCFC-22 fact sheet says: "Most air conditioners have a nameplate on the unit that identifies the refrigerant it contains and other information, such as safety certifications and electrical ratings."

    Source: EPA fact sheet: Residential Air Conditioning and the Phaseout of HCFC-22, What You Need to Know

Safety

  1. 52. A high-pressure system with a hermetic compressor has been pulled into a deep vacuum. What do EPA's Type 2 safety topics say about the compressor at this point?

    • A. Run it briefly to confirm that the vacuum holds
    • B. Energize it to help pull the vacuum deeper
    • C. Energize it to boil moisture out of the oil
    • D. Leave it de-energized while it is under vacuum
    Show answer

    Answer: D. Leave it de-energized while it is under vacuum

    EPA's Type 2 safety topics state: "Shouldn't energize hermetic compressors under vacuum".

    Source: EPA: Section 608 Technician Certification Test Topics

  2. 53. A high-pressure system is installed in an equipment room. Which equipment room requirement under ASHRAE Standard 15 do EPA's Type 2 safety topics name?

    • A. An oxygen deprivation sensor, only with flammable refrigerants
    • B. A carbon monoxide detector, with all refrigerants
    • C. An oxygen deprivation sensor, with all refrigerants
    • D. A refrigerant odorant injector, only with HFC refrigerants
    Show answer

    Answer: C. An oxygen deprivation sensor, with all refrigerants

    EPA's Type 2 safety topics list "Equipment room requirements under American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Standard 15 (oxygen deprivation sensor with all refrigerants)".

    Source: EPA: Section 608 Technician Certification Test Topics