OSHA's general industry rule 29 CFR 1910.253 covers cylinder manifolds in paragraph (c), "Manifolding of cylinders". What does it require for fuel-gas and oxygen manifolds, portable outlet headers and manifold operation? This post reads the eCFR text up to date as of November 25, 2026. It is an explainer, not a rule change, and it does not cover the construction rules in 29 CFR 1926 Subpart J.
How much fuel gas can one manifold hold inside a building?
"Manifolds shall be approved either separately for each component part or as an assembled unit" (c)(1)(i). Except as provided in (c)(1)(iii), fuel-gas cylinders connected to one manifold inside a building are limited to a total capacity of 300 pounds (135.9 kg) of liquefied petroleum gas or 3,000 cubic feet (84 m³) of other fuel-gas (c)(1)(ii). More than one such manifold may share a room "provided the manifolds are at least 50 feet (15 m) apart or separated by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour" (c)(1)(ii).
A manifold above those totals "shall be located outdoors, or in a separate building or room constructed in accordance with paragraphs (f)(6)(i)(H) and (f)(6)(i)(I) of this section" (c)(1)(iii). Separate manifold buildings or rooms, which may also store calcium carbide drums and fuel-gas cylinders as (b)(3) provides, "shall have no open flames for heating or lighting and shall be well-ventilated" (c)(1)(iv). "High-pressure fuel-gas manifolds shall be provided with approved pressure regulating devices" (c)(1)(v).
What applies to high-pressure oxygen manifolds?
Paragraph (c)(2) covers oxygen manifolds "for use with cylinders having a Department of Transportation service pressure above 200 psig (1.36 MPa)". They also need approval (c)(2)(i).
- Location: "Oxygen manifolds shall not be located in an acetylene generator room." They are kept a minimum distance of 20 feet (6.1 m) from fuel-gas cylinders or combustible materials (especially oil or grease), or behind the same kind of barrier (c)(2)(ii).
- Capacity: Except as provided in (c)(2)(iv), oxygen cylinders on one manifold are limited to a total gas capacity of 6,000 cubic feet (168 m³), with the same 50-foot or barrier rule for several manifolds in a room (c)(2)(iii).
- Larger manifolds: One with more than 6,000 cubic feet connected "should be located outdoors or in a separate noncombustible building". The rule says should here, not shall. If it is inside a building having other occupancy, it "shall be located in a separate room of noncombustible construction having a fire-resistance rating of at least one-half hour or in an area with no combustible material within 20 feet (6.1 m) of the manifold" (c)(2)(iv).
- Bulk systems: An oxygen manifold or oxygen bulk supply system with storage capacity of more than 13,000 cubic feet of oxygen (measured at 14.7 psia and 70 °F) connected in service or ready for service, or more than 25,000 cubic feet including unconnected reserves on hand at the site, must comply with NFPA No. 566-1965 (c)(2)(v).
- Regulators: "High-pressure oxygen manifolds shall be provided with approved pressure-regulating devices" (c)(2)(vi).
What applies to low-pressure oxygen manifolds?
Paragraph (c)(3) covers cylinders with a DOT service pressure not exceeding 200 psig. These manifolds must suit oxygen at 250 psig, have a minimum bursting pressure of 1,000 psig and a safety relief device relieving at no more than 500 psig (c)(3)(i). Hose and hose connections subject to cylinder pressure must meet (e)(5), and hose must have a minimum bursting pressure of 1,000 psig (c)(3)(ii).
"The assembled manifold including leads shall be tested and proven gas-tight at a pressure of 300 psig (2.04 MPa)", and the test fluid "shall be oil-free and not combustible" (c)(3)(iii). Location follows (c)(2)(ii) through (c)(2)(v) (c)(3)(iv). This sign must be conspicuously posted at each manifold (c)(3)(v):
Low-Pressure Manifold
Do Not Connect High-Pressure Cylinders
Maximum Pressure—250 psig (1.7 MPa)
When can portable outlet headers be used?
"Portable outlet headers shall not be used indoors except for temporary service where the conditions preclude a direct supply from outlets located on the service piping system" (c)(4)(i). Also:
- Each piping outlet supplying a header has a readily accessible shutoff valve (c)(4)(ii), and master shutoff valves for oxygen and fuel-gas sit at the header's entry end (c)(4)(iv).
- Fuel-gas headers need an approved hydraulic back-pressure valve at the inlet, unless each outlet has an approved regulator, check valve or back-pressure valve as listed in (c)(4)(v).
What does the rule say about operating a manifold?
- Installation is supervised by someone familiar with proper practice (c)(5)(i); parts serve only the gases they are approved for (c)(5)(ii).
- When acetylene cylinders are coupled, "approved flash arresters shall be installed between each cylinder and the coupler block". The exception: "For outdoor use only, and when the number of cylinders coupled does not exceed three, one flash arrester installed between the coupler block and regulator is acceptable" (c)(5)(iii).
- Fuel-gas cylinders on a portable manifold inside a building may not exceed 3,000 cubic feet of gas (c)(5)(iv).
- "Acetylene and liquefied fuel-gas cylinders shall be manifolded in a vertical position" (c)(5)(v).
- Cylinders discharged together through a common manifold must have pressures "approximately equal" (c)(5)(vi).
Where can I study the rest of Subpart Q?
Our OSHA general industry welding study guide covers other Subpart Q topics; it notes that manifolds are not covered there in detail. See also the service piping explainer, the hose and regulator explainer and our welding page. OSHA rules are safety requirements, not a welding certification exam; this post does not describe any certification test.